Direct connection of up to 20 m (66′) without needing to amplify the signal to the HI 7638 probe
- Automatic diagnostic controls
- Available in four models, each with a different measurement range
- Operational mode LED indicators
- Automatic Temperature Compensation with HI 7638 potentiometric conductivity probe with built-in temperature sensor
- Transparent splash-proof cover included
These controllers allow direct connection of a potentiometric conductivity probe
(HI 7638) with a cable up to 20 m long, without needing a transmitter to amplify the signal.
The output configuration for connecting a recorder or a PLC can be chosen between
0-20 or 4-20 mA.
The LED on the front panel indicates the operating status of the controller.
The Automatic Temperature Compensation (ATC) is performed directly by the HI 7638 probe with built-in temperature sensor.
The front panel is protected behind a transparent splash-proof cover.
Order Information:
The HI 943500 series is supplied complete with mounting brackets and instructions.
Manual: Download
Specification :
Range | 0 to 1999 µS/cm | |
Resolution | 1 µS/cm | |
Accuracy @ 20°C | ±2% F.S. | |
Calibration | manual, two point, through offset and slope trimmers | |
Temperature Compensation |
automatic, 0 to 60°C (32 to 140°F), with ß=2%/°C | |
Recorder Output | 4-20 mA (isolated) | |
Setpoint Relay | 1, isolated, 2A, max. 240 V, resistive load, 1,000,000 strokes | |
Alarm Relay | 1, isolated, 2A, max. 240 V, resistive load, 1,000,000 strokes | |
Power Supply | 115 or 230 VAC ±10% (user selectable); 50/60 Hz | |
Enclosure | black anodized aluminum body; front panel with flame retardant ABS; transparent splash-proof front cover | |
Environment | -10 to 50°C (14 to 122°F); RH max 95% | |
Panel Cutout | 141 x 69 mm (5.6 x 2.7’’) | |
Weight | 1 kg (2.2 lb.) |